Extract engineering data
Turn panel schedules, specifications, and single-line diagrams into structured tables and workbooks.
Electrical engineering toolkit
MTAI-Web helps engineers extract data from PDFs, search technical libraries, and design panel layouts — with secure sign-in and private, per-user workspaces.
New here? Create an account on the sign-in page — an administrator will approve it.
Turn panel schedules, specifications, and single-line diagrams into structured tables and workbooks.
Find datasheets and coordination tables, and download official PDFs when you need them.
Sketch panel layouts in a 2D editor, place reusable blocks, save named drawings, and export images.
Run conversions and sizing checks, and pick the right device from embedded catalogs.
Sign-ups are reviewed by an administrator before access is granted.
Each user sees only the tools their level allows.
Sign-ins and tool usage are logged so admins can review activity.
MTAI-Web is an in-browser electrical engineering toolkit maintained by Eng. Mohamed Tamer. For access requests, feedback, or support, contact Eng. Mohamed Tamer.
Your personal dashboard — favorites, recent work, and quick search.
The MTAI electrical engineering toolkit, running entirely in your browser. Upload a PDF and instantly pull out panel schedules, specifications and single-line diagrams — your files stay on your device, and nothing is uploaded anywhere.
Paste ABB Product IDs — one per line, or full https://new.abb.com/products/… links — and download every datasheet PDF as a single ZIP. PDFs are generated by ABB and saved straight to your browser's download folder.
Extract panel headers and circuit rows from panel-schedule PDFs, review corrected tables and export a formatted Excel workbook.
Extract electrical specification fields from tender/offer PDFs and export a verified workbook.
Extract load tables and panel data from Single Line Diagram PDFs.
Upload an ABB quotation PDF. Text pages are read right away; if the PDF is a scan, it's read automatically too — and you can export an editable copy of the result.
Search ABB's motor, selectivity and back-up coordination tables and download the official table PDFs — served from the MTAI storage, or generated live when not stored yet.
Technical reference for electrical engineering standards, definitions, and best practices
A short circuit is an abnormal low-impedance connection between two nodes of an electric circuit that are meant to be at different voltages. This forces excessive current to flow through the path of least resistance, bypassing the intended load.
In low-voltage installations supplied by transformers, the short-circuit current has two components:
IEC 60947-2 defines four key short-circuit performance ratings for low-voltage circuit breakers. Each answers a different question about fault handling:
The difference is in the rigor of the test:
O = Opening (break) operation | CO = Close-Open (make then break) | t = time interval (minimum 3 minutes)
IEC 60947-2 Table 1 defines the minimum Ics percentages allowed for each utilization category:
| Ics (% of Icu) | Category A Instantaneous | Category B Time-Delayed |
|---|---|---|
| 25% | ✔ | — |
| 50% | ✔ | ✔ |
| 75% | ✔ | ✔ |
| 100% | ✔ | ✔ |
| Category | Behavior | Icw | Typical Devices |
|---|---|---|---|
| A | No intentional short-time delay for selectivity. Instantaneous tripping on fault. | Normally not declared | MCBs, standard MCCBs |
| B | Designed for selectivity with intentional short-time delay. Withstands fault current for a defined period. | Key rating (kA / time) | ACBs, heavy-duty MCCBs |
Icm is the peak current the breaker can safely close onto. It is always greater than Icu because of the DC offset in the first cycle of a fault. Under IEC 60947-2:
Where n depends on the test power factor (which relates to the X/R ratio of the fault circuit):
| Icu Range | Test cos φ | n Factor | Example |
|---|---|---|---|
| 6 kA < Icu ≤ 10 kA | 0.50 | 1.7 | 10 kA → 17 kA peak |
| 10 kA < Icu ≤ 20 kA | 0.30 | 2.0 | 20 kA → 40 kA peak |
| 20 kA < Icu ≤ 50 kA | 0.25 | 2.1 | 50 kA → 105 kA peak |
| Icu > 50 kA | 0.20 | 2.2 | 65 kA → 143 kA peak |
At the secondary terminals of a MV/LV distribution transformer, the three-phase symmetrical short-circuit current can be calculated using the transformer's rated parameters:
where In = transformer rated current, Usc = short-circuit impedance voltage (%)
where Zpu = Usc% / 100, VLL = line-to-line secondary voltage
For a 1000 kVA transformer, 400V secondary, Usc = 6%:
At any point downstream, the cable impedance adds to the transformer impedance, reducing the fault current:
| Standard | Scope | Key Ratings |
|---|---|---|
| IEC 60947-2 | Industrial circuit-breakers (skilled/instructed persons, ≤1000V AC / ≤1500V DC) | Icu, Ics, Icw, Icm |
| IEC 60898-1 | Household MCBs (uninstructed persons, residential/commercial) | Icn, Ics |
| IEC 61439-1 | Low-voltage switchgear and controlgear assemblies (panels, switchboards) | SCP rating, Icw for assemblies |
| IEC 60909 | Short-circuit current calculation method (all voltage levels) | Ik", Ik, Ipk, m/n factors |
| IEC 60947-3 | Switch-disconnecters | Icw (1s preferred) |
When selecting a circuit breaker, verify these ratings in order of importance:
| Application | 1st to Verify | 2nd to Verify | 3rd to Verify | Notes |
|---|---|---|---|---|
| Final distribution / branch circuit | Icu or Icn | Ics | Rated current + trip curve | Icw usually not relevant |
| Motor feeder | Icu | Ics | Icm (if closing onto fault) | Check motor starting current |
| Industrial MCCB feeder | Icu | Ics | Trip-unit settings | High Ics improves post-fault confidence |
| Main incomer | Icu | Ics | Icw (if time-delay selectivity) | Often needs coordination study |
| ACB incomer / bus-tie | Icw | Icu / Ics | Icm | Selectivity + making duty central |
| Transfer / auto source switching | Icm | Icu | Ics | Closing onto existing downstream fault |
Circuit breaker reference and panel layout design tools.